Tia Portal | V17 Hsp New ((top))
To update your TIA Portal V17 Hardware Support Packages (HSP)
, you need to download the specific files from the Siemens support site and integrate them into your hardware catalog. This process allows you to configure new modules or firmware versions not included in your original installation. 1. Download New HSPs
You can obtain the latest support packages directly from the Siemens Industry Online Support (SIOS) portal. Direct Download : Visit the Support Packages for TIA Portal (HSP) Siemens SiePortal Version Selection : Ensure you download the package specifically labeled for TIA Portal V17 . The files typically have a extension. Extract Files
: If the download is a ZIP archive, extract the files to a local folder on your engineering station. 2. Install via TIA Portal Software Once you have the files, follow these steps to import them: Open TIA Portal : Launch the software but do open a specific project yet (or close any active projects). Access Settings : Go to the menu and select Support Packages Add from System : Click the "Add from file system" Select Files
: Browse to the folder where you extracted the HSP files, select the required files, and click
: In the "Detailed information" list, select the packages you just added and click
Note: You must close all TIA Portal instances before the installation can finish. 3. Alternative: Use TIA Administrator / Updater tia portal v17 hsp new
If you have an active internet connection on your engineering PC, you can automate this: TIA Administrator Totally Integrated Automation UPDATER Navigate to the Support Packages "Check for updates" "Find Support Packages" Select the new HSPs from the list and click "Download and install" Troubleshooting & Tips Restart Required
: After manual installation, you must restart TIA Portal for the new hardware to appear in the hardware catalog. Legacy Versions
: If you are working with older hardware, check if you need the HSP for STEP 7 V5.x System Compatibility : TIA Portal V17 is officially supported on Windows 10
. If you are using Windows 11, ensure you have installed the latest V17 Updates (e.g., Update 5 or 6) for better stability. Industrial Monitor Direct specific module
(like a new S7-1500 CPU or ET 200SP head module) that isn't showing up in your catalog?
How do you update the hardware catalog in TIA Portal? - ID: 54163658 To update your TIA Portal V17 Hardware Support
To update your TIA Portal V17 hardware catalog, you can download the latest Hardware Support Packages (HSPs) directly from the Siemens Industry Online Support (SIOS) portal. As of early 2026, the cumulative update files remain available to ensure compatibility with newer modules and firmware versions. Latest Update Information Current Version: V1.29 (dated June 24, 2025).
Complete Package: TIA_Portal_V17_HSP.zip (approx. 433.8 MB) contains all available HSPs for V17.
Incremental Update: TIA_Portal_V17_HSP_DiffToLastVersion.zip (approx. 67.9 MB) includes only the most recently added support files. New Hardware Supported in Recent V17 HSPs
HSP0311 V3.0: SIMATIC ET 200SP F-TM ServoDrive/StepDrive (FW V2.0). HSP0379: SIMATIC S7-1500 TM NPU (FW V2.0). HSP0424: SIMATIC IPC477E PRO. HSP0341: SIMATIC ET 200SP, TM PTO 2x24V. HSP0357: SIMATIC ET 200SP AI RTD/TC HF (FW V2.1). How to Install
Download & Unzip: Visit the Siemens HSP Download Page (Entry ID: 72341852) and download the ZIP file. Extract it to a local folder. Open TIA Portal: Navigate to Options > Support packages.
Add from File System: Click the "Add from file system" button and browse to the extracted .isp17 files. Open a project in TIA Portal V17
Install: Select the desired packages from the list, click "Install", and close all TIA Portal instances when prompted to complete the process.
Alternatively, if your engineering station has internet access, use the TIA Software Updater (Start > Siemens Automation > Totally Integrated Automation UPDATER) to find and install these packages automatically.
When you see "HSP New" in the context of TIA Portal, it generally refers to adding support for newer Siemens hardware devices (like the latest S7-1200 CPUs, HMI panels, or Drives) to an older version of the TIA Portal software. Since TIA Portal V17 is not the newest version, you will almost certainly need to install HSPs to use hardware released after V17 launched.
5. Verifying the Installation
After installing the new HSP, you should verify that the new hardware appears in your catalog.
- Open a project in TIA Portal V17.
- Open the Device Configuration of a station (e.g., double-click "PLC_1").
- Open the Hardware Catalog on the right side.
- Click the Filter icon (funnel) or search for the specific device.
- Look for a Green Arrow icon or a version number next to the device. If it appears without a warning triangle, the HSP was installed successfully.
Issue 1: "New" Hardware is Grayed Out
If you see the hardware in the catalog but cannot drag it in, or it is grayed out:
- Cause: The HSP might require a specific Firmware version for the CPU.
- Solution: Check the device properties. You may need to update the firmware of the actual physical device via an SD card or Web Server before TIA can configure it.
Guide: Managing and Installing HSPs in TIA Portal V17
2. ET 200SP Firmware Version 6.0 Modules
Distributed I/O is the backbone of modern factories. The latest HSP brings support for ET 200SP modules with firmware version 6.0, which includes improved IO-Link master functionality and enhanced diagnostic alarms.
Another helpful HSP feature:
"Consistent Library Handling" – When you use HSP-supported devices, the master copies in the global library are updated automatically, so dragging a new drive (like SINAMICS G220) into your project correctly brings in all its parameters and telegrams.
"Direct Online & Diagnostics for New Hardware"
Once you install the latest HSP for V17, you can:
- Go online with a new controller (e.g., S7-1200 G2 or a new S7-1500 CPU variant) that V17 didn't originally support.
- Perform hardware detection and upload the exact configuration from the physical device.
- Use all diagnostic views (module status, diagnostic buffer, DP/DN topology) for that new hardware.